Absolyte® GP

Absolyte® is one of the world's best-selling large valve-regulated, lead-acid (VRLA) battery brands.

Design life in years: 20 @ 25°C
Nominal capacity: 104–4800 Ah @ 25°C
Grid plate
Single cell
Valve regulated lead-acid batteries
Maintenance-free (no topping-up)
Special high current performance
Recyclable

 

  • System ampere-hour range – 104 to 4800 Ah to 1.75 VPC at 8-hour rate @ 25°C (77°F).
  • Electrolyte – 1.310 specific gravity acid (nominal).
  • Safety vent – 3-10 psi opening pressure, self-resealing.
  • Terminals – Solid copper insert.
  • Positive plate – Patented lead calcium tin silver alloy.
  • Negative plate – Lead calcium grid alloy.
  • 20 years design life in float applications at 25°C (77°F)
  • 1200 cycles to 80% DOD at 25°C (77°F)
  • Operating temperature – Temperature excursions between -40°C (-40°F) to +50°C (122°F) allowed (battery performance and life will be affected).
  • Self-discharge – 0.5 to 1% per week maximum @ 25°C (77°F).
  • Float voltage – 2.23 to 2.27 VPC.
  • Container and Cover - Polypropylene is standard. Flame retardant, UL94 V-0/28% L.O.I. is optional.
  • Enhanced post access for maintenance and battery health assessment

 

Absolyte® GP Industrial Batteries Section 26.05

Absolyte® GP Batteries Constant Current Specifications (104-4800Ah, 1 min to 24 h) Section 26.10

Absolyte® GP Batteries Constant Current Specifications (104-4800Ah, 12 h to 120 h) Section 26.10B

Absolyte® GP Batteries Constant Power Specifications Section 26.10C 2010-12

Absolyte® GP Single Cells Modules Specifications Section 26.12

Absolyte® GP for Photovoltaic & Alternative Energy Applications Section 62.61 2013-09

Absolyte® GP Relay Rack Specs Section 26.13 2011-02

Absolyte® GP Installation and Setup of a GNB® Absolyte® IIP/Absolyte® GP Non-Seismic Relay Rack System Z99-ABSRELAYRACK Rev AB 2008-08

Absolyte® GP Installation and Operating Instructions Section 92.61 2013-09

Basic Operating and Maintenance Instructions for Absolyte® Batteries GB3917 2010-12

Basic Operating and Maintenance Instructions for Absolyte® Batteries in Railroad Signal Service in English and French GB3710EF 2010-11L

Basic O&M Instructions for Absolyte® Batteries in Railroad Signal Service GB3915ES 2010-12

Absolyte® GP Single Cells and Monitor Charger Section 63.01

 

GP cells

 

Type

Nominal
Voltage

Capacities

Dimensions
approx.

Weight
approx.

 

 

C8
@ 1.75 VPC
@ 25°C

L

W

H

 

 

V

Ah

in

in

in

Lbs

1-100G39

2

1800

20.0

8.55

26.4

329

1-100G45

2

2088

22.2

8.59

26.4

375

1-100G51

2

2400

24.5

8.59

26.4

424

1-100G57

2

2688

26.8

8.59

26.4

470

1-100G63

2

3000

29.1

8.59

26.4

516

1-100G69

2

3288

31.3

8.59

26.4

563

1-100G75

2

3600

33.6

8.59

26.4

609

1-100G81

2

3888

35.8

8.59

26.4

653

1-100G87

2

4200

38.0

8.59

26.4

704

1-100G93

2

4488

40.3

8.59

26.4

750

1-100G99

2

4800

42.6

8.59

26.4

796

 

GP blocks

 

Type

Nominal
Voltage

Capacities

Dimensions
approx.

Weight
approx.

 

 

C8
@ 1.75 VPC
@ 25°C

L

W

H

 

 

V

Ah

in

in

in

Lbs

3-100G13

6

600

20.0

8.55

26.4

329

3-100G15

6

696

22.2

8.59

26.4

375

3-100G17

6

800

24.5

8.59

26.4

424

3-100G19

6

896

26.8

8.59

26.4

470

3-100G21

6

1000

29.1

8.59

26.4

516

3-100G23

6

1096

31.3

8.59

26.4

563

3-100G25

6

1200

33.6

8.59

26.4

609

3-100G27

6

1296

35.8

8.59

26.4

653

3-100G29

6

1400

38.0

8.59

26.4

704

3-100G31

6

1496

40.3

8.59

26.4

750

3-100G33

6

1600

42.6

8.59

26.4

796

6-50G05

12

104

17.3

8.55

16.3

157

6-50G07

12

152

21.7

8.55

16.3

210

6-50G09

12

208

26.2

8.55

16.3

252

6-90G07

12

256

21.7

8.55

23.6

316

6-50G13

12

312

35.2

8.55

16.3

358

6-90G09

12

344

26.2

8.55

23.6

397

6-90G11

12

432

30.8

8.55

23.6

477

6-90G13

12

520

35.2

8.55

23.6

558

6-90G15

12

608

39.7

8.59

23.6

638